  management interface the management interface for this pdu model is transitioning to a new technology platform. the new interface can be distinguished by a usb-a port (for envirosense2 modules) in place of the round?envirosense?port. for managing the units containing the round port, tripp lite recommends using the poweralert console launcher rather than a web browser. this application enables local access of the pdu using a self-contained, compatible java runtime environment version. the console launcher can be downloaded for free; click the above link or go to the management solutions / utilities page. units with the new interface work will with most current web browsers. 2.3-2.9kw single-phase switched pdu with lx platform network interface, 200-240v (8 c13), c14, 200-240v input, 6.5ft cord, 1u rack-mount, taa model number: PDUMH15HVNET description tripp lite switched pdu / power distribution unit offers advanced network control and monitoring with the ability to turn on, turn off, recycle or lock-out power to each individual receptacle, monitor site electrical conditions and remotely monitor output power consumption. supports remote control and custom notification of user-specified conditions. individually switched outlets can be controlled in real-time to remotely reboot unresponsive network hardware, or be custom programmed for user-defined power-up and power-down sequences to ensure proper startup of interdependent it systems and prevent inrush- related overloads as network equipment is first energized. unused pdu outlets can be electronically locked off to prevent the connection of unauthorized hardware. pdu output current consumption in amps is displayed locally via visual meter and remotely via web/network interface to warn of potential overloads before critical it mains or branch breakers trip. features 200/208/230/240v switched power distribution unit / pdu with built-in web/network interface (15a maximum; agency de-rated to 12a 200/208/240v and 10a at 230v) l c14 power inlet accepts a wide variety of worldwide input cord options l includes 6.5 ft. / 2m c14 cable l 1u horizontal rackmount form factor l highlights switched 10/12a 200-240v pdu; 1u horizontal rackmount l lx platform network interface l visual current meter; reversible housing l c14 inlet; 6.5ft / 2m c14 power cable included l 8 c13 switched outlets with cord retention brackets l temperature, humidity and contact-closure monitoring options l taa compliant l package includes 1u switched pdu l mounting brackets l cord retention plates l c13 to c14 power cable l 1 / 4
specifications 8 switched c13 outlets l supports power-on, power-off or reboot of each outlet on a real-time or programmable basis l enables reboot of locked equipment, custom power-on/power-off sequences, load-shedding of optional loads and disabling unused outlets l lx platform network interface provides pdu control and data regarding input voltage and output load levels l in-rack environmental reporting with optional temperature, humidity and contact-closure sensor options l 10/100 mbps auto-sensing l included cord retention brackets keep vital network equipment plugged in and continuously powered l overview upc code 037332139276 pdu type switched output output capacity details 2.5kw (208v), 2.3kw (230v) / 12a (10a ce) total capacity frequency compatibility 50 / 60 hz output receptacles (8) c13 output nominal voltage 208; 230 overload protection n/a customized load management receptacles 8 individually switched output receptacles input pdu input voltage 208; 230 recommended electrical service 12a 208v; 10a 230v maximum input amps 15 maximum input amps details agency de-rated to 12a at 200, 208, 220 & 240v; agency de-rated to 10a at 230v pdu plug type iec-320 c14 input cord length (ft.) 6.5 input cord length (m) 1.98 input phase single-phase user interface, alerts & controls front panel lcd display digital display reports total pdu output current in amps 2 / 4
front panel leds 8 leds display power on-off status for each output receptacle switches n/a physical minimum required rack depth (inches) 17.1 minimum required rack depth (cm) 43.43 shipping dimensions (hwd / in.) 5.70 x 20.70 x 23.00 shipping dimensions (hwd / cm) 14.48 x 52.58 x 58.42 shipping weight (lbs.) 13.20 shipping weight (kg) 5.99 unit dimensions (hwd / in.) 1.75 x 17.3 x 14.8 unit dimensions (hwd / cm) 2,87 x 43,9 x 37,6 unit weight (lbs.) 9.00 unit weight (kg) 4.08 material of construction metal form factors supported 1u rackmount. includes mounting accessories for 2-4 post racks pdu form factor horizontal (1u) environmental storage temperature range 5 to 122f (-15 to 50c) relative humidity 5-95% non-condensing operating elevation (ft.) 0-10,000 operating elevation (m) 0-3000 communications snmp compatibility pre-installed lx platform interface provides remote monitoring via java-free html5 web interface, telnet, ssh and snmp management systems special features tvss grounding back panel grounding lug certifications certifications tested to ul/can 60950-1 (usa, canada), fcc / en class a (emissions), nom (mexico), ce (iec 60950), rohs compliant, taa compliant warranty product warranty period (worldwide) 2-year limited warranty 3 / 4
? 2019 tripp lite. all rights reserved. all product and company names are trademarks or registered trademarks of their respective holders. use of them does not imply any affiliation with or endorsement by them. tripp lite has a policy of continuous improvement. specifications are subject to change without notice. tripp lite uses primary and third-party agencies to test its products for compliance with standards. see a list of tripp lite's testing agencies: https://www.tripplite.com/products/product-certification-agencies 4 / 4


▲Up To Search▲   

 
Price & Availability of PDUMH15HVNET

All Rights Reserved © IC-ON-LINE 2003 - 2022  

[Add Bookmark] [Contact Us] [Link exchange] [Privacy policy]
Mirror Sites :  [www.datasheet.hk]   [www.maxim4u.com]  [www.ic-on-line.cn] [www.ic-on-line.com] [www.ic-on-line.net] [www.alldatasheet.com.cn] [www.gdcy.com]  [www.gdcy.net]


 . . . . .
  We use cookies to deliver the best possible web experience and assist with our advertising efforts. By continuing to use this site, you consent to the use of cookies. For more information on cookies, please take a look at our Privacy Policy. X